Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

  • Supported Models

Model

Communication Method

DSE 7320



RS485

DSE 7450 Battery Plant

DSE 7320 MKII

DSE 7410 MKII

DSE 6620

DSE857 adapter extension is needed.
Please make contact with your supplier and Galooli support team
https://galooli.atlassian.net/l/cp/v1duJaCC

DSE 4521

DSE 4520

DSE 6610

DSE 4510

DSE 6120

DSE 6110

DSE 6012

DSE 6020

DSE 6010

DSE 7220

  • Network configuration

Device Baudrate

19200

  • Supported Services

Parameters

Alarm Name

Alarm Criticality

Remote Controlling

Engine_Hours

low oil pressure

critical

TBA

Grid_Voltage_Phase_1-3

emergency stop

critical

Battery_Voltage

low coolant

observation

Engine_Speed

high coolant

urgent

Frequency

over speed

urgent

Voltage_Phase_1-3

under speed

urgent

Current_Phase_1-3

over freq.

urgent

Coolant_Temperature

under freq.

urgent

Oil_Pressure

high voltage

urgent

Working_Mode

low voltage

urgent

Total_Output_KWH

high battery

urgent

low battery

urgent

fail to start

critical

alternator fail

urgent

fail to close

observation

fail to stop

urgent

Child pages (Children Display)