The Request

...

  • Locate all of the off-grid hybrid sites where the batteries are in use less than 25% of the day. This indicates inefficient use of batteries and is therefore considered to be a site that is not utilizing its full energy potential.

  • After that conduct a detailed analysis of one of the sites you identified and create a report that displays the status of all the energy components in this site in order to determine why the batteries are only working for a short period of time. There can be a number of reasons, such as: the batteries are defective or the site consumes more energy than the batteries can providethe battery capacity does not correspond to the site's consumption.

The Solution

  1. Open the Galooli Pro Application.

  2. In order to locate an off-grid and hybrid site with batteries that are used for less than 25% of the day, you should run a summary report on all the organization, using two 3 different fields, a calculation field and a filtering methods.

    • Using the Run the report for a period of seven days.

    • Add a "Site LayoutLayout" field to find only the text "Offgrid" and “Hybrid”. In order to accomplish this, you will need to use a "Regular Expression” method.

    • Using the Add a "Usage Time Battery" field to find batteries usage under six hours ( 25% of the day.

    • Add a “Duration (Days)” field.

...

  1. Select one unit from the list of results and verify that the data matches what you anticipated.

  2. To understand the status of all the energy components on site and, ultimately, determine why the batteries are only functioning for a short period of time, please run the following detailed report for one week on the selected unit:

  3. Add a “Recorded Digital Inputs” - "Site_Global.Generator_1_Running" field, allowing you to determine whether the generator is running and when it is running.

    • Add a “Recorded Digital Inputs” - "Site_Global.Battery_Discharging" field, in order to be able to determine whether the batteries are discharging and when they are discharging.

    • Add a “Recorded Analog Inputs-Site_Global.Battery_SOH” field, which will allow you to examine the health of the battery and determine whether the problem lies with the battery itself.

    • Add a “Recorded Analog Inputs-Site_Global.Battery_SOC” field, in order to determine if the battery discharges and charges as expected. For example, batteries begin discharging at 85% and stop at 40%.

    • Add a “Recorded Analog Inputs-Site_Global.Battery_Temperature” field, to determine whether the battery temperature is within the normal range.

    • Add a “Recorded Analog Inputs” - “Site_Global.Consumers_Load_Power [W]” field, which will allow you to view the load that is created by the energy consumers.

    • Add a “Recorded Analog Inputs” - “Site_Global.Battery_Power [W]” field, which displays the power provided by the batteries

  4. Use the "Detailed Graph" view in order to gain a full understanding of the site's operational status.
    תמונה!