A rectifier parameter result can be viewed in the "Result Table" after you select the "Get" operation and run the address. The parameters will be added to the table separately each time you run a different OID.

...

(warning)As you can see in the picture above, we are able to get the value of the “System Voltage” via the Rectifier. The value that we receive from the Cut Through is "5132", now we need to take this value and convert it to the ratio given next to the relevant OID on the Power Center.

To do this, take the last five digits of the OID from the MIB browser, locate the OID in Power Center, look at the ratio, and determine the value (5132/10=513)

...

Set Parameters

(warning) It is important to verify that the parameters can be edited before attempting to modify them

Upon selecting the "Set" operation and running the address, a new window will appear allowing you to modify the parameter value.

(warning)Using the Power Center, you must convert the new value according to the ratio described there (50.50 multiplied by 100 equals 5050).

...