The Cut Trough to the rectifier allows you to get data and even set it depending on the data types.
...
Cut Trough Progress
Download the “MIB BROWSER” - https://www.ireasoning.com/download.shtml Browser” - SNMP Monitoring Software.
Open the Power Center >> Connect to the Elara gateway via serial/OTA connection >> Click on “Read Configuration” >> Click on “Status” . >> Click on “Status” tab. Now you can see all the information about the rectifier that connected to the Elara gateway.
להעתיק הצידה שלושה מרכיבים
Click on “Direct-Comm” >> Choose “Ethernet (SNMP: LOCALHOST) >> Ensure that the "Gateway", "Destination IP", and "Elara IP" are accurate >> Leave the “Power CenterDirect-Comm” window open.
4. Open the “MIB Browser” platform >> Type “localhost” in the address box >> Click on “Advanced” >> In the window that appears, type the correct “Read Community” and “Write Community” >> Click “Ok”
...
5. The "OID" for the relevant data field should be written in the appropriate location. An "OID" represents a specific field address of dataa parameter. Obtaining the OID can be accomplished by contacting the rectifier company.
...
In the event that you wish to obtain data via the OID, please select "Get" and then "Go".
In the event that you wish to set data via the OID, please select “Set” and then “Go”“Go”
...
7. You can view the rectifier results in the result table. Each time you run a different OID, the data will be added separately to the table.
...
8. To "set" data in the rectifier , double click the relevant row and you will be presented with a window for editing the data.
Editing is only possible for the relevant parameters mentioned above.
...