The graph shows the trend of the fuel efficiency rates - the average values per site per day of L/Gallon per hour and L/Gallon per kWh. In addition, shows the trend of the average generators hours per site per day.
Most Inefficienct Generators
Load SplitLoad Split
The dashabord calculates the average operating load for each site over the selected time period. In order to calculate the operating load, the average actual power of the generator is divided by the apparent power (KVA) (and a power factor of 0.8). Because the apparent power of a generator is a function of its size, low/high operating loads can indicate a problem with the generator's sizing. 60%-80% is the recommended operating load for the generator, to optimize the generator's helath and fuel efficiency.
The generator's KVA can be configured by the user. If there is no value configured, the site will be counted as "No Load Information" in the pie.
Most Inefficienct Generators
The most inefficient generators in terms of fuel consumption (L/Gallon) per energy production (kWh)/