Field Name | Field Meaning and Logic |
---|---|
Grid Power | Energy assets such as grids, generators, and batteries can be monitored through multiple data sources - meters, control panels, etc. A global field considers all data sources and prioritizes them. Those fields will be used in the system for the displays, source logic, and summary fields (and as a result - in the system dashboards). |
DG 1/2 Load Power | |
Battery Power | |
Consumers Load Power | This field sums up all the power which is being consumed on site. The result value is the maximal value between the tenants' power to the rectifiers' power, added to the power of all the air conditioners on site. |
Sources Load Power | This field sums up all the power produced by energy assets on-site - grid, generators, and solar. |
Entrance_Configured | Indicates whether the alarm has been configured or not False - Not configured True - Configured |
Entrance_Alarm | Indicates if the site entrance gate/door is open False - Entrance open True - Entrance close |
Alarm_Consumers_Load_Drop | If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active |
Page Comparison
General
Content
Integrations
App links