Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Field Name

Field Meaning and Logic

Grid Power

Energy assets such as grids, generators, and batteries can be monitored through multiple data sources - meters, control panels, etc. A global field considers all data sources and prioritizes them. Those fields will be used in the system for the displays, source logic, and summary fields (and as a result - in the system dashboards).

DG 1/2 Load Power

Battery Power

Consumers Load Power

This field sums up all the power which is being consumed on site. The result value is the maximal value between the tenants' power to the rectifiers' power, added to the power of all the air conditioners on site.

Sources Load Power

This field sums up all the power produced by energy assets on-site - grid, generators, and solar.

Entrance_Configured

Indicates whether the alarm has been configured or not

False - Not configured

True - Configured

 

Entrance_Alarm

Indicates if the site entrance gate/door is open

False - Entrance open

True - Entrance close

Alarm_Consumers_Load_Drop

If Site_Global.Consumers_Load_Power < 50% of Consumers Load Average power than alarm active