Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

Name of the lesson

AC meters and AC Current Transformer Rings

Purpose of the lesson

During this lesson, you will learn how to choose the correct AC meter and current transformer ring for your site

Target Audience

Service providers, back-office, organization managers, technicians, etc.

What to expect at the end of the lesson

The user will acknowledge:

  • Which AC meters and Current Transformer Rings does Galooli provide

  • Which AC meters are suitable for which Current Transformer Rings

  • How to choose the perfect AC Meter and Current Transformer Ring for my site

  • How accurate are the AC Meter and the AC ring

  • How to install the AC meters and Current Transformer Rings on site

Info

It is highly recommended to go through the contents in the order in which they appear

Which AC meters and Current Transformer Rings does Galooli provide?

Galooli supports a variety of AC meters and Current Transformer Rings according to the changing needs of the users, different currents, amount of phases, conversion ratio, and the diameter of the AC cables.

The meters can include an entry for the AC cable or meters that require the use of Current Transformer Rings.

Current Transformer Rings can be used with cables of varying diameters, some of which have an open and close mechanism.

Info

Read more:
AC Meters:
CE Transducer CE42
CE Transducer CE42CT
Carlo Gavazzi EM210

AC Current Transformer Rings:
CE-CTH Split Core
Rogowski CT

Which AC meters are suitable for which Current Transformer Rings?

(tick) CE Transducer CE42 AC meter works without any Current Transformer Ring however, the cable entry can
be too narrow for some cable's diameter.

(tick) CE Transducer CE42CT AC meter works best with the CE-CTH Split Core rings. Specifically with the rings
that has a conversion ratio of 1A

(tick) Carlo Gavazzi EM210 AC meter works best with the Rogowski CT rings.

How to choose the accurate AC Meter and Current Transformer Ring for my site?

There are a couple of questions you should answer to choose the most suitable AC Meter and Current Transformer Ring:

  • What is the current that needs to be measured?

  • How many phases does the energy source have?

  • What is the conversion ratio?

  • What is the diameter of a cable that needs to be measured?

    The following table allows you to easily choose the required products.
    Catalog numbers are internal to Galooli.

Ring Diameter/Current

≤ 30A

≤ 50A

≤ 150A

≤ 200A

≤ 4000A


≤ 11 mm

CE Transducer CE42

No Current Transformer Ring needed


(error)


≤ 24 mm

CE Transducer CE42CT
+
CE-CTH Split Core (24mm/30A)

CE Transducer CE42CT
+
CE-CTH Split Core (24mm/50A)

CE Transducer CE42CT
+
CE-CTH Split Core (24mm/150A)


(error)


(error)


≤ 36 mm

CE Transducer CE42CT
+
CE-CTH Split Core (36mm/30A)

CE Transducer CE42CT
+
CE-CTH Split Core (36mm/50A)

CE Transducer CE42CT
+
CE-CTH Split Core (36mm/150A)


(error)


(error)


≤ 350 mm

Carlo Gavazzi EM210
+
Rogowski CT (350mm)


≤ 600 mm

Carlo Gavazzi EM210
+
Rogowski CT (600mm)


≤ 900 mm

Carlo Gavazzi EM210
+
Rogowski CT (900mm)

How accurate are the AC Meter and the AC ring?

Item Codes/Data

Meter
Accuracy

Ring
Accuracy

Accuracy
Calculation

Galooli Item Code

Voltage reading
accuracy

Current reading
accuracy

CT
Accuracy

Overall voltage
accuracy

*Overall current accuracy

*Overall kwh
accuracy

CE Transducer CE42CT (Meter)

0.50%

0.50%

Not relevant

CE-CTH Split Core 24mm/30A (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.60%

CE-CTH Split Core 24mm/50A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

2.10%

CE-CTH Split Core 24mm/150A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

CE-CTH Split Core 36mm/30A (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.60%

CE-CTH Split Core 36mm/50A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

2.10%

CE-CTH Split Core 36mm/150A (Ring)

0.50%

0.50%

0.50%

0.50%

1.00%

1.50%

**CE Transducer CE42 (Meter)

0.50%

0.50%

Not relevant

1.00%

***400-AcRin150A5A-502 (Ring)

0.50%

0.50%

1.00%

0.50%

1.50%

2.00%

***400-AcRin50A5A-502 (Ring)

0.50%

0.50%

3.00%

0.50%

3.50%

4.00%


*Overall current accuracy = Meter current reading accuracy + CT Accuracy

*Overall kwh accuracy = Overall voltage accuracy + Overall current accuracy

**The meter can measure current and voltage without a CT ring

***These rings are not available for sale

(info) Calculation Examples
In order to see the calculation method and ensure that the data for the units are correct for you, please
refer to the attached Excel file. You should download the Excel file to your computer.

View file
nameAC.xlsx

What is the best way to install the AC meters and Current Transformer Rings on site?

The installation process of the AC Meter and Current Transformer Ring needs to be accurate and in the right order for the current measurement will be correct.

You will find a lot of important information about the AC Meter and Current Transformer Ring installation process in the “Read more” section.

Info

Read more: