/DG/solar/battery/an unknown source /DG/solar/battery/unknown (Asset)_(Asset), where (Asset) is grid/DG/solar/battery/an unknown source/Min /Min generator's coolant temperature

Field Name

Field Description

Calculation Method

Avail. Time Grid

Total time (hours) the grid was available

Based on records where Site_Global.Grid_Available = Yes.

At the end of the document, there are comments regarding availability.

Avail. Time Solar

The total Total time (hours) the solar supplied power which was greater than 0 kWh 0W to the site.

Based on records where one of the fields Rectifier_X.Solar Power [W] was greater than 0.

At the end of the document, there are comments regarding availability.

Avail. Time Battery

Grid Avail. Period Count

Grid Avail. Avg. Period Time

Total time (hours) the battery was available.

Usage Time Grid

The total time (hours) the grid

was contributing to the site's load. This is the time the grid

was on load, multiplied by the part load it supplied (between 0-100%).

Based on records where Site_Global_Grid_On_Load = Yes, multiplied by the value of Site_Global_

Grid_Load [%].

At the end of the document, there are comments regarding availability.

Usage Time DGX

The total time (hours) generator X was contributing to the site's load. This is the time the generator was on load, multiplied by the part load it supplied (between 0-100%).

Based on records where Site_Global_DGX_On_Load = Yes, multiplied by the value of Site_Global_

DGX_Load [%]

.

At the end of the document, there are comments regarding availability.

Usage Time Solar

The total time (hours) the solar was contributing to the site's load. This is the time the solar was on load, multiplied by the part load it supplied (between 0-100%).

Based on records where Site_Global_Solar_On_Load = Yes, multiplied by the value of Site_Global_Solar_Load [%].

At the end of the document, there are comments regarding availability.

Usage Time DGX

Usage Time Solar

Usage Time Battery

Usage Time Unknown

Battery

The total time (hours) the battery was contributing to the site's load. This is the time the battery was on load, multiplied by the part load it supplied (between 0-100%).

Based on records where Site_Global_Battery_On_Load = Yes, multiplied by the value of Site_Global_Battery_Load [%].

At the end of the document, there are comments regarding availability.

Usage Time Unknown

The total time (hours) an unknown source was contributing to the site's load. This is the time the unknown source was on load, multiplied by the part load it supplied (between 0-100%).

Based on records where Site_Global_Unknown_On_Load = Yes, multiplied by the value of Site_Global_Unknown_Load [%].

At the end of the document, there are comments regarding availability.



Site Down Time


The total time there was an active PLD or LVD alarm, and the rectifier's 1 current was less than the average current of the rectifier in the previous day.

Based on the records where Site_Global.DC_Status_PLD = Yes or Site_Global.DC_Status_LVD = Yes, and Rectifier_1.I_Load [A]

At the end of the document, there are comments regarding availability.

Grid - PhX V Min/Max/Avg [V]

The minimum, maximum, and average voltage of the grid phase for the selected time range.

Grid - PhX A Min/Max/Avg [A]

The minimum, maximum and average current of the grid phase for the selected time range

Grid - kWH Initial/Final [KWH]

The first/last record of the kWh value that was read from the grid AC meter, for the selected time range.

Based on the detailed field AC_Meter_Grid.Total_KWH [KWH]




Grid - kWH Total [KWH]




The total kWh production of the asset for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

Grid - PhX Power Factor Max/Min [A]

The minimum, maximum and average power factor of the ATS phase for the selected time range.

ATS - PhX V Min/Max/Avg [V]

The minimum, maximum, and average voltage of the ATS phase for the selected time range.

ATS - PhX A Min/Max/Avg [A]

The minimum, maximum and average current of the ATS phase for the selected time range

ATS - kWH Initial/Final [KWH]

The first/last record of the kWh value that was read from the ATS AC meter, for the selected time range.

Based on the detailed field AC_Meter_ATS.Total_KWH [KWH]




ATS - kWH Total [KWH]




The total kWh of that was read from the ATS meter for the selected time range.

Based on the detailed field AC_Meter_ATS.Total_KWH [KWH].

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

ATS - PhX Power Factor Max/Min [A]

The minimum, maximum and average power factor of the ATS phase for the selected time range.

DGX - PhX V Min/Max/Avg [V]

The minimum, maximum, and average voltage of the generator phase for the selected time range.

DGX - PhX A Min/Max/Avg [A]

The minimum, maximum and average current of the generator phase for the selected time range

DGX - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the generator AC meter, for the selected time range.

Based on the detailed field AC_Meter_Generator_X.Total_KWH [KWH]

DGX - kWh Total [KWH]

The total kWh production of the asset generator for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

DGX - PhX Power Factor Min/Max

[A]

The minimum, maximum and average power factor of the phase for the selected time range.

DGX - Coolant Temp Min/Max

[Celsius]

The minimum and the maximum coolant temperature of the

geenrator X.


DGX - Min, Max, Min, Avg Load [KW]

The minimum, maximum and average load of the geenrator for the selected time range. Generator load (kW) is used to measure the real electric power provided by the generator.

Monitoring the generator load is necessary for assuring the generator is operating under the proper conditions, reducing maintenance costs and frequent replacements.

SOLAR - PhX V Min/Max/Avg [V]

The minimum, maximum, and average voltage of the solar meter phase for the selected time range.

SOLAR - PhX A Min/Max/Avg [A]

The minimum, maximum and average current of the solar meter phase for the selected time range

SOLAR - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the solar AC meter, for the selected time range.

Based on the detailed field Meter_Solar.Total_KWH [KWH]




SOLAR - kWh Total [KWH]




The total kWh production of the asset solar for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

SOLAR_Module X V Max/Avg [V]

The maximum and average voltage of the solar module for the selected time range.

Based on the detailed fields Rectifier_Y.Solar_Voltage_X [V]

X=1->4, Y=1->5

SOLAR_Module X V Avg [V]SOLAR_Module X I Max/Avg [A]

The maximum and average current of the solar module for the selected time range.

Based on the detailed fields Rectifier_X.Solar_Current_X [V]

X=1->4, Y=1->5

SOLAR_Module X I Avg [A]

WIND - PhX V Min/Max/Avg [V]

The minimum, maximum, and average voltage of the wind meter per phase, for the selected time range

WIND - PhX A Min/Max/Avg [A]

The minimum, maximum and average current of the wind meter per phase, for the selected time range

WIND - kWh Initial/Final [KWH]

The first/last record of the kWh value that was read from the wind phase AC meter, for the selected time range.

Based on the detailed field Meter_Wind.Total_KWH [KWH]




WIND - kWh Total [KWH]




The total kWh production of the asset wind turbine for the selected time range.

The kWh difference between the 2 subsequent records will be aggregated, only if it is positive, and if the extrapolation of the value for the total kWh of the day is less than 7500 kWh. The extrapolation is checking if the kWh difference is reasonable, so if all day that was the kWh production rate, the total kWh for that day was less than 7500 kWh.

Meaning, only if 24*d(kWh)/d(time) < 7500 kWh

...