IOs Configuration
Double-click the unit that you wish to configure.
Navigate to the IOs tab.
Create two IOs (Analog input for the fuel measurement and Digital input for the fuel sensor connection status):
Analog input:
a. Select site_global.fuel_X.
b. Check the main fuel tank.
c. Give it a meaningful name.
d. Select the relevant calibration table via the magnifying glass button.
e. Apply to save the data.
...
Digital input:
a. Choose site_global.fuel_1_disconnected.
b. Give it a meaningful name.
c. Display text: use connected“connected-disconnecteddisconnected”.
d. Apply to save.
...
Live Display Configuration
Select the relevant unit on the organization tree.
Navigate to live display.
Select the config button.
Under “Section: Generator”, check the “Fuel 1” and/or “Fuel 2”
...
5. Navigate to the “Live Display” tab.
6. Check the “Layout Display” button.
7. Validate the fuel level indication
...
8. Record the fuel level value and input it in the calibration calculator section.
If we get a match, continue to the next document
Else, If we don’t, redo the calibration process.
...
9. Save the table with the name of the site